Installation
  1. Position strainer to match flanged connections.
  2. When alignment is correct (inlet and outlet headers), flanges can be bolted when appropriate gaskets are placed between the flanges.
  3. When the unit is bolted to the pipes, supports to the strainer should be bolted to the floor.
Operation
    1. Strainer should be filled with fluid slowly, while venting the air.
    2. When the strainer is filled, vents should be closed. Both chambers need to be filled.
    3. Rotate hand wheel to the stop. This will permit the inflow to enter only one side leaving the other basket clean and ready to handle the flow should the basket straining become clogged.
    4. To change over to the clean basket, rotate the hand wheel in the opposite direction until the stop is contacted.
    5. If used, pressure gages indicate pressure loss. When differential reaches 10 PSI, change to the clean side.
    6. When the dirty side basket needs to be removed, the following steps need to be observed:
      • After translating the valves to the clean side, the dirty side can be addressed.
      • Bleed the pressure from the side containing the dirty basket. CAUTION: Never attempt to remove cover while vessel contains any pressure.
      • Unbolt cover and remove basket. Care should be taken not to damage cover gasket.
      • Basket can be cleaned by washing with a hose line.
      • Return cleaned basket to strainer immediately and secure cover. This action will make the strainer ready should the other basket become clogged.
Maintenance
  1. Keep basket screens clean for best performance.
  2. Maintain extra gaskets for blind covers and o-rings for quick open covers.
  3. A spare basket screen allows for shorter downtime in production
Service Recommendation

The Duplex strainer is designed for use in fluid handling systems where the flow cannot be shut off for basket cleaning.

Features

The duplex strainer features four butterfly valves or Ball Valves for positive shutoff of one body while the other body continues to filter your flow of liquids. The butterfly valves or Ball Valves can be independently operated or can be lined and synchronized using one gear operator to rotate all at the same time. The baskets have a large capacity, which allows longer periods of time between cleanings. The single basket design is easily and quickly cleaned. Standard basket material is stainless steel with special materials available on application.

Construction

Strainers body parts are made from Seamless Pipes, Plates, welded pipe and forged flanges.